DC 125A fuse with a 48V trip coil and auxiliary contacts
To protect 125A direct current circuits by disconnecting a single connection (positive or negative). The built-in trip coil allows for remote disconnection of the fuse by applying a voltage of 48-60V to the coil contacts.
This voltage is adapted to the voltage of a 16S LiFePO4 pack, which eliminates the need for an additional power supply.
An additional pair of contacts makes it easy to create an alarm system that indicates when the protection has been triggered.
- Rated Working Voltage Ue 100V
- Rated Current In 125A
- Rated Insultation Voltage Ui 500V
- Rated Impulse Withstand Voltage Uimp 6kV
- Tripping Type Thermal Magnetic
- Rated Ultimate Short-Circuit Breaking Capacity Icu 6/10kA
- Rated Service Short-Circuit Interrupting Capacity lcs6/7.5kA
- Electrical Life Actual 4000
- Mechanical Life Actual 20000
- Overvoltage Category III
- Pollution degree 3
- Ingress Protection IP40; Wiring port IP20
- Resistance to humidity and heat Class 2
- Relative Humidity: 95%
- Terminal capacity 2.5~35mm2
- Tightening Torque of Terminals 2.0~2.5 N·m
- Ambient Temperature -30°C-70°C
- Storage Temperature -40°C-85°C
- Installation Method DIN
- Coil control voltage 48-60V.
- Auxiliary contact load capacity 3A/415V AC.