A 250A DC fuse is two 125A DC fuses that are locked together and connected in parallel.
They are therefore suitable for protecting 250A circuits by disconnecting one connection (positive or negative).
Maximum operating voltage is 100V.
| Rated working voltage |
Ue | 100V |
| Rated current | In | 250A |
| Rated insulation voltage | Ui | 500V |
| Rated impulse Withstand Voltage | Uimp | 6kV |
| Tripping characteristics |
B/C | |
| Tripping type |
Thermal magnetic | |
| Rated Ultimate Short-Circut Breaking Capacity |
Icu | 6/10kA |
| Rated service Short-Circut Breaking Capacity |
lcs | 6/7.5kA |
| Mechanical life | Actual | 4000 Cycles |
| Standard | 1000 Cycles | |
| Mechanical life | Actual | 20000 Cycles |
| Standard | 7000 Cycles | |
| Overvoltage Category | Ili | |
| Pollution degree |
3 | |
| Ingress Protection | IP40; Wiring port IP20 | |
| Resistance to humidity and heat | Class 2 | |
| Relative Humidity | e:;;95% | |
| Vibration | acc. to IEC60068-2-6 | |
| Shocks | acc. to IEC60068-2-27 | |
| Terminal capacity | 2.5~35mm2 | |
| Tightening Torque of Terminals | 2.0~2.5 N·m | |
| Ambient temperature | -30°C-70°C | |
| Storage temperature | -40°C-85°C | |
| Installation Method | DIN | |
| Weight | 316.4g |